Gamewell-FCI 600 series

From The Fire Panel
600 series
Manufacturer

The Gamewell Company
Gamewell-FCI {"label": "Manufacturer", "field": "The Gamewell Company
Gamewell-FCI"}

Communication protocol

XP95
SmartScan
Velociti {"label": "Communication protocol", "field": "XP95
SmartScan
Velociti"}

Introduced

1994 {"label": "Introduced", "field": "1994"}

Discontinued

2015 {"label": "Discontinued", "field": "2015"}

Preceded by

Gamewell Identifire Network System 2
Gamewell Zone Network System
Flex Series
Gamewell ZANs 200 and 400 {"label": "Preceded by", "field": "Gamewell Identifire Network System 2
Gamewell Zone Network System
Flex Series
Gamewell ZANs 200 and 400"}

Succeeded by

Gamewell-FCI E3 series
Gamewell-FCI S3 series {"label": "Succeeded by", "field": "Gamewell-FCI E3 series
Gamewell-FCI S3 series"}

The Gamewell-FCI 600 series was a series of panels originally developed by The Gamewell Company.

History

The 600 series was introduced by The Gamewell Company in 1994 with a new SmartStart™ autoprogramming feature.[1][2] The original series consisted of the Flex 620, IdentiFlex 630, and IdentiFlex 650, and the IdentiFlex models used the XP95 addressable protocol.

In 1998, Gamewell introduced the AM-500 card for IdentiFlex 650 systems to simplify replacements for the Flex 500. The card ran the same Cerberus protocol as the old Flex 500.

In late 1998, Gamewell introduced the IdentiFlex 610.[3]

In 2001, Gamewell replaced the IdentiFlex 630 with the IdentiFlex 632.[4]

The 610VE voice evacuation system was also introduced in 2001. In early 2002, CAB-VE voice evacuation systems for the IdentiFlex 632 were introduced.[5]

In 2003, shortly after being acquired by Honeywell, the IdentiFlex 602 was introduced.[6]

In late 2004, the Flex 620 was discontinued.[7]

In October 2004, the IdentiFlex 602SS and 610SS were introduced. They were the first panels to use the SmartScan™ protocol (Gamewell's version of CLIP). This allowed them to utilize compatible System Sensor detectors and modules. The IF632 and IF650 series were also given SmartScan capable models.[8]

In December 2004, Gamewell introduced the IdentiFlex 602VE voice evacuation panels.[9] These panels used the XP95 protocol.[10]

Between 2009 and 2010, after becoming Gamewell-FCI in 2005, the IdentiFlex 610, 632 and 650 series panels and their SmartScan equivalents were replaced by the E3 Series.[11] The IF602SS was discontinued at the end of 2011, and the IF602 was discontinued in 2015.[12][13][14] Both were replaced with the S3 series.

Models

Name Protocol SLCs (included/maximum) Built-in NACs Replaced
IF602-126R[15] XP95 1/2 4
IF602-126XL XP95 1/2 4
IF602VE-126[16] XP95 1/2 4
IF602VE-126Z XP95 1/2 4
IF602-252R XP95 2/2 4
IF602-252XL XP95 2/2 4
IF602VE-252 XP95 2/2 4
IF602VE-252Z XP95 2/2 4
IF602SS-198R[17] SmartScan 1/2 4
IF602SS-198XL SmartScan 1/2 4
IF602SS-396R SmartScan 2/2 4
IF602SS-396XL SmartScan 2/2 4
IF610-126[18] XP95 1/4 4
IF610-126XL XP95 1/4 4
IF610-126VE[19] XP95 1/4 4
IF610-252 XP95 2/4 4
IF610-252XL XP95 2/4 4
IF610-252VE XP95 2/4 4
IF610-504 XP95 4/4 4
IF610-504XL XP95 4/4 4
IF610-504VE XP95 4/4 4
IF610SS-396[20] SmartScan 2/4 2
IF610SS-396XL SmartScan 2/4 2
IF610SS-792 SmartScan 4/4 2
IF610SS-792XL SmartScan 4/4 2
IF630-126[21] XP95 1/4 2
IF630-252 XP95 2/4 2
IF630-504 XP95 4/4 2
IF632[22][23] XP95/SmartScan 0/8 2
IF632-126 XP95 1/8 2 IF630-126
IF632-252 XP95 2/8 2 IF630-252
INS 2
INS 2AP
INS 2P
INS-2F
INS-2APF
INS-2PF
IF632-378 XP95 3/8 2
IF632-504 XP95 4/8 2 IF630-504
INS 2E
INS 2EAP
INS 2EP
INS-2EF
INS-2EAPF
INS-2EPF
IF632-630 XP95 5/8 2
IF632-756 XP95 6/8 2
IF632-882 XP95 7/8 2
IF632-1008 XP95 8/8 2
IF654[24][25] XP95/SmartScan 0/16 2
IF658 XP95/SmartScan 0/16 2

Replacements

Old model Cabinet Main board Loop expansion boards Main LCD Power supply
IF602-126R SLP-RETROFIT SLP-RB SLC95-PM LCD-SLP FLPS-7-RB
IF602-126XL IF600XL-RETROFIT[26] ILI95-MB-E3 None
IF602VE-126 IF600-RETROFIT ILI95-MB-E3 None
IF602VE-126Z IF600-RETROFIT ILI95-MB-E3 None
IF602-252R SLP-RETROFIT SLP-RB SLC95-PM (x2) LCD-SLP FLPS-7-RB
IF602-252XL IF600XL-RETROFIT ILI95-MB-E3 None
IF602VE-252 IF600-RETROFIT ILI95-MB-E3 None
IF602VE-252Z IF600-RETROFIT ILI95-MB-E3 None
IF602-198R SLP-RETROFIT SLP-RB SLC-PM LCD-SLP FLPS-7-RB
IF602SS-198XL IF600XL-RETROFIT ILI-MB-E3 None
IF602-396R SLP-RETROFIT SLP-RB SLC-PM (x2) LCD-SLP FLPS-7-RB
IF602SS-396XL IF600XL-RETROFIT ILI-MB-E3 None
IF610-126 IF600-RETROFIT ILI95-MB-E3 None
IF610-126XL IF600XL-RETROFIT ILI95-MB-E3 None
IF610-126VE IF600-RETROFIT ILI95-MB-E3 None
IF610-252 IF600-RETROFIT ILI95-MB-E3 None
IF610-252XL IF600XL-RETROFIT ILI95-MB-E3 None
IF610-252VE IF600-RETROFIT ILI95-MB-E3 None
IF610-504 IF600-RETROFIT ILI95-MB-E3 ILI95-S-E3
IF610-504XL IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3
IF610-504VE IF600-RETROFIT ILI95-MB-E3 ILI95-S-E3
IF610SS-396 IF600-RETROFIT ILI-MB-E3 None
IF610SS-396XL IF600XL-RETROFIT ILI-MB-E3 None
IF610SS-792 IF600-RETROFIT ILI-MB-E3 ILI-S-E3
IF610SS-792XL IF600XL-RETROFIT ILI-MB-E3 ILI-S-E3
IF632 IF600XL-RETROFIT
IF632-126 IF600XL-RETROFIT ILI95-MB-E3 None
IF632-252 IF600XL-RETROFIT ILI95-MB-E3 None
IF632-378 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3
IF632-504 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3
IF632-630 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3 (x2)
IF632-756 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3 (x2)
IF632-882 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3 (x3)
IF632-1008 IF600XL-RETROFIT ILI95-MB-E3 ILI95-S-E3 (x3)
IF654
IF658

References

  1. https://web.archive.org/web/20080512201708/http://www.gamewell-fci.com/history.html
  2. https://nfpa.access.preservica.com/uncategorized/IO_0e046c77-793f-4938-8f6a-41decce04c28/
  3. https://web.archive.org/web/19990828060851/http://gamewell.com/pr981228_610intro.htm
  4. "Product Information Page - The Gamewell Company" Gamewell. Archive 2001-04-05 vs. 2001-12-15
  5. "Product Information Page - The Gamewell Company" Gamewell. Archive 2001-12-15 vs. 2002-04-05
  6. "Gamewell - Fire Control Systems - Products - Intelligent / Addressable Systems" Gamewell. Archive 2003-08-05 vs. 2003-10-12
  7. "Gamewell - Fire Control Systems - Products - Intelligent / Addressable Systems" Archive 2004-08-14 vs. 2004-09-15
  8. "Gamewell - Fire Control Systems - Products - Intelligent / Addressable Systems" Gamewell. Archive 2004-09-15 vs. 2004-10-11
  9. "Gamewell - Fire Control Systems - Products - Intelligent / Addressable Systems" Gamewell. Archive 2004-12-12 vs. 2004-12-15
  10. "IdentiFlex 602VE Analog Addressable Control Panel with Voice Evacuation" (CS-2497). Gamewell (December 9, 2004).
  11. "Gamewell-FCI - Products - Product Lines - Analog/Networking - IdentiFlex 600 Series" Gamewell-FCI. Archive 2009-04-09 vs. 2010-09-20
  12. https://cdn2.hubspot.net/hubfs/121714/Orrprotection_Docs_Feb2016/FCI_Discontinue_Notice_for_7200_FV7200_FN72_Fire_Panel.pdf
  13. https://web.archive.org/web/20151004172441/http://www.gamewell-fci.com/products/analog-networking.html
  14. https://web.archive.org/web/20151023011839/http://www.gamewell-fci.com/en-US/Pages/Category.aspx?cat=HFS-GAMEWELLFCI&category=Analog/Networking
  15. "IdentiFlex 602 Analog Addressable Control Panel" (CS-2401). Gamewell (October 21, 2003).
  16. "IdentiFlex 602VE Analog Addressable Control Panel with Voice Evacuation" (CS-2497). Gamewell (December 9, 2004).
  17. "IdentiFlex 602 with SmartScan™ Analog Addressable Control Panel" (CS-2490). Gamewell (November 19, 2004).
  18. "IdentiFlex 610 Analog Addressable Control Panel" (CS-2001). Gamewell (October 9, 2003).
  19. "Emergency Voice Evacuation VE/VEX Options for IF610 and IF632 Analog Addressable Control Panel" (CS-2002). Gamewell (2001).
  20. "IdentiFlex 610 with SmartScan™ Analog Addressable Control Panel" (CS-2491). Gamewell (April 8, 2005).
  21. "IdentiFlex 630 Analog Addressable Control Panel" (3200). Gamewell (October 1996).
  22. "IdentiFlex 632 Analog Addressable Control Panel" (CS-2004). Gamewell (March 9, 2004).
  23. "IdentiFlex 632 with SmartScan™ Analog Addressable Control Panel" (CS-2492). Gamewell (February 15, 2005).
  24. "IdentiFlex 650 Analog Addressable Control Panel" (CS-2005). Gamewell (April 8, 2005).
  25. "IdentiFlex 650 with SmartScan™ Analog Addressable Control Panel" (CS-2493). Gamewell (February 17, 2005).
  26. "Gamewell Retfrofit Kits" (9021-60678). Honeywell International Inc. (September 2017).