Fire-Lite MS/FireWatch 5000 series
The Fire-Lite MS/FireWatch 5000 series is a small lineup of conventional fire alarm control panels that each have an integrated digital alarm communicator transmitter (DACT). These panels are similar to the FireWatch 411UDAC, but are also quite different at the same time.

Features
- DTMF keypad used on all FireWatch 5000 series panels
- Programmable zones
- Can be programmed as a fire panel only (0), slave communicator only (1), or a fire panel/communicator (2). These modes can be can be changed at Address 56.
- Condition history mode
- Troubleshooting mode
- Annunciator compatibility (RZA-5F on 50xx, LED-10 on 5210UD)
- Remote Site Upload/Download (UD models only)

Reporting Formats
Express and Ademco Contact ID formats allow complete transaction to be communicated in under five seconds. The panels support dual line pulse or DTMF DACT interfaces to the PSTN. The formats supported are listed below.
- 20 PPS, 3+1 standard and expanded.
- 20 PPS, 4+1 standard and expanded.
- 20 PPS, 4+2 standard and expanded.
- 4+1 and 4+2 Ademco Express.
- Ademco Contact ID (UD models only)

Specifications
MS-5012
- 5 Zones
- 1 NAC
- 12 Volt Operation
- 1.0A Current Output
MS-5024
- 5 Zones
- 2 NACs
- 24 Volt Operation
- 3.0A Current Output
MS-5024UD
- 5 Zones
- 2 NACs
- 24 Volt Operation
- 3.0A or 5.0A Current Output
- Remote Site Upload/Download (Modem Required)
MS-5210UD
- 10 Zones
- 2 NACs (expandable to 4)
- 24 Volt Operation
- 3.0A or 6.0A Current Output
- Remote Site Upload/Download (Modem Required)
- EIA-485 Bus
- LED-10IM required for EIA-485 interface devices (LED-10, AFM-16F, ACM-8RF, LDM series)
Useful Commands
All commands spell out abbreviations on DTMF keypad. The format is listed as (number command - word - function).
6676 - NORM - Returns the panel to its normal state
7764 - PROG - Enters programming mode
9255 - WALK - Enters walk-test mode
4478 - HIST - Views the history log
8768 - TROU - Enters troubleshooting mode, activates internal voltmeter
5267 - LAMP - Conducts a system lamp test
3472 - DISA - Disables a zone, one at a time. This makes the panel go into trouble.
3622 - ENAB - Enables a zone that has previously been disabled
3745 - DRIL - Fire drill function